Panduola TechLiquid Cooling Quick Disconnects

Testing & Quality

UQD testing evidence, presented with clear scope

Panduola Tech presents available test references carefully: current public data covers UQD02 / UQD04 / UQD06 / UQD08 and should not be treated as a universal certification for every series.

UQD02UQD04UQD06UQD08
Cleanroom testing and production environment reference
Testing and production environment reference image; public claims remain limited to the verified UQD report scope.

16

Original source test PDFs reviewed

4

Covered UQD models

10

Samples per model in mechanical-life records

>=5,000

Mating cycles with leakage checks passed

2025-11-15

Flow resistance

Original records cover deionized-water flow-resistance testing in the plug-to-socket direction. Pressure-loss curves were generated across a 0-1 bar range at 1 L/min intervals.

2025-11-17

Burst pressure

Original burst-pressure records cover three samples per model and show minimum measured values above each stated requirement.

2026-04-13

Mechanical life

Original mechanical-life records cover 10 samples per model. All covered models reached at least 5,000 mating cycles and passed pressure leakage checks after testing.

2026-04-27

Insertion force

Original insertion-force records cover three samples per model and show maximum measured values within each model's specified mating-force limit.

Burst pressure test

ModelMinimum burst pressureRequirementSafety marginResult
UQD022730 psi>= 870 psi / 60 bar3.14xPass
UQD041590 psi>= 696 psi / 48 bar2.28xPass
UQD061452 psi>= 300 psi / 20.7 bar4.84xPass
UQD08583 psi>= 300 psi / 20.7 bar1.94xPass

Insertion force test

ModelMaximum insertion forceRequirementResult
UQD0259.2 N<= 60 NPass
UQD0464.4 N<= 65 NPass
UQD0683.5 N<= 90 NPass
UQD0894.5 N<= 135 NPass

What the data supports

It is fair to say the covered UQD models have available source records for flow resistance, burst pressure, mechanical life, leakage checks, and insertion force.

It is not appropriate to describe this as universal certification for all series or all customer applications.

Final product choice should still be checked against the drawing, fluid, working pressure, temperature range, and installation requirements.

16 original source PDFs reviewed: four UQD models times four test categories.

Public-facing values are shown under Panduola Tech and standardized for overseas B2B communication.

Original submitting-party names are retained only in private source records and are not used as public website brand claims.

Obvious source-record wording inconsistencies were corrected in the English customer-facing version without changing measured values.